Delta UPS System. Fully integrated power solutions in one 42U cabinet for small data center applications. 24x34x78.
***INCLUDES EATON ELECTRICAL DISTRIBUTION PANEL***
High Integration and Space Saving
• Fully integrated in one 42U cabinet with power supply, battery
runtime, static transfer switch and input/output/bypass breakers
Ultimate Availability
• Fully modularized design and hot-swappable modules for easy
deployment and maintenance
• Redundant aux power and controller design
• Dual CAN bus to ensure the inherent reliability on signal level
• Battery module’s LED fuse warning indicators can alert
operators in the event of a blown fuse
Excellent Power Performance
• Industry-leading high power density of power module: 15
kVA/kW in 2U height
• AC-AC conversion efficiency 95% and ECO mode efficiency up
to 98.5% with Energy star 2.0 certificated
• Green mode for effective utilization
High Manageability
• Environment Management System integration (optional)
• Power consumption trend calculation
• Inbuilt Ethernet and RS485 communication interface
• User-friendly 10” touch panel
Technical Specifications
Model DPH-60K-LV DPH-105K-LV
Power Rating kVA / kW 15, 30, 45, 60 15, 30, 45, 60, 75, 90, 105
Power Module Quantity 4+1 redundancy 7+1 redundancy
Battery Module Quantity Inbuilt 16 pcs (4 strings) Modular battery cabinet
Input Nominal Voltage 208/120 Vac, 220/127 Vac (3 phase, 4-wire +G)
Voltage Range 166~253 Vac (full load)
iTHD < 5% (non-linear); < 3%(linear) *
Power Factor > 0.99
Frequency 50/60 Hz (Auto-Selectable)
Output Voltage 208/120 Vac, 220/127 Vac (3 phase, 4-wire +G)
Voltage Regulation ±1% (static); ±5% (dynamic)
Power Factor Unity
THDv < 2% (Linear); < 5% (Non-linear)
AC-AC Efficiency 95%
ECO Efficiency Up to 98.5%
Overload Capability ≤ 125%: 10 minutes; ≤ 150%: 1 minute; > 150%: 1 second
Display 10” Touch Panel
Battery Nominal Voltage ±168 Vdc (±14 pcs)
Charge Voltage ±190 Vdc (adjustable from 182 Vdc to 196 Vdc)
Charge Current 6A Max. per power module
Environment Operating Temperature 32 to 104°F (0 to 40°C)
Storage Temperature -13 to 167°F (-25 to 75°C)
Relative Humidity 5~95% non-condensing
Audible Noise < 68 dBA **
Others Compliance UL 1778, FCC Class A, Energy Start 2.0
Parallel Maximum 4 units
Communication Interface Ethernet, RS485
Physical Dimensions (W x D x H) 23.62” x 33.46” x 78.74” (600 x 850 x 2000 mm)
Weight: UPS System 562.2 lb (255 kg) 619.5 lb (281 kg)
Weight: 15 kW Power Module 46.3 lb (21 kg / 1 pc)
Weight: Battery Module 51.8 lb (23.5 kg / 1 pc, 1 battery module=9 Ah battery x 7 pcs)
Modular Battery
Cabinet
Dimensions (W x D x H) 23.62” x 33.46” x 78.74” (600 x 850 x 2000 mm)
Weight: w/ Full Battery Module 2123.1 lb (963 kg)
Weight: w/o Battery Module 465.2 lb (211 kg)
Maximum Number of Battery Strings 8
Maximum Number of Battery Modules 32
* When input voltage total harmonic distortion input is less than 1%